Permit: T07CM02529

Parcel: 13818017C

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
02/13/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
12/13/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
RETROFIT ALL PA STRAPS. OKAY TO WRAP.
12/07/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) BRACED PANELS REQUIRED NORTH AND SOUTH EXTERIOR WALLS OVER 75' SPAN OR LET IN BRACES
2) CLIP ALL HEADERS
3) NAIL PROTECT PLUMBING
4) PER TRUSS RAKE AND BRACING DETAIL OSB ON GABLE ENDS
5) 2 ABS PER BRACED PANEL
6) PROVIDE TRUSS CALCS