Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T07CM02522

Parcel: 135074540


Addresses:

1820 S RESEARCH LP


Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T07CM02522

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/16/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
11/15/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- PROVIDE A FRESH AIR INTAKE ON AC UNIT
- PROVIDE COVERS OVER CANVAS CONNECTORS
- PAINT EXPOSED PVC
- PROVIDE SCREEN IN T-TOP ON ROOF
- PROVIDE A GUARD RAIL AT ROOF HATCH AS PER 304.10 2006 IMC