Permit: T07CM02515

Parcel: 115180970


Addresses:

1230 N 13TH AV

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/29/2008 BUILDING - FINAL Approved IVRS - Inspection :*
04/03/2008 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO HAVE ALL RECEPTACLES CHECKED FOR OPEN GROUNDS AND NEUTRALS
2) WIRING FROM BEDROOM NEEDS TO BE IN EMT OR CONDUIT GOING INTO SERVICE PANEL ON OUTSIDE OF HOUSE
3) NEED TO INSTALL BATTERY OPERATED SMOKE DETECTORS
4) NEED KNOCKOUT COVER PLUGS OR BREAKERS IN UNUSED OPENINGS
5) NEED TO REMOVE OR RELOCATE LIGHT IN CLOSET