Permit: T07CM02494

Parcel: 21134016C


Addresses:

3511 S SANDARIO RD

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/24/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
07/07/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
NO BOND REQUIRED
OK TO CLEAR BLD #202, 208, 209
TRICO ELECTRIC
07/03/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WHERE IS THE UFER? NOT CONNECTED TO SERVICE AS REQUIRED IN 250 NEC (GROUNDING ELECTRODE CONDUCTOR)
2. ALSO, ADDRESS DOES NOT CORRESPOND WITH PERMIT ADDRESS (ADDRESS ON SERVICE) #202?
3. SELF TAPPING SHEETMETAL SCREWS NOT APPROVED FOR GROUNDING
4. BLD. LOCKED, PLANS SHOULD BE ON SITE AT BLD. TO BE INSPECTED
5. RECALL INSPECTION AFTER CORRECTIONS MADE
05/13/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/29/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK GROUNDING & CONDUITS BELOW BLD. SLAB #202
04/23/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PLEASE LABEL DISCONNECT OR METER AS TO BLD. #
03/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
02/29/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
WHEN CALLING INSP. LEAVE MSG. AS TO WHAT YOU WANT INSPECTED.