Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/24/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 07/07/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NO BOND REQUIRED OK TO CLEAR BLD #202, 208, 209 TRICO ELECTRIC |
|
| 07/03/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. WHERE IS THE UFER? NOT CONNECTED TO SERVICE AS REQUIRED IN 250 NEC (GROUNDING ELECTRODE CONDUCTOR) 2. ALSO, ADDRESS DOES NOT CORRESPOND WITH PERMIT ADDRESS (ADDRESS ON SERVICE) #202? 3. SELF TAPPING SHEETMETAL SCREWS NOT APPROVED FOR GROUNDING 4. BLD. LOCKED, PLANS SHOULD BE ON SITE AT BLD. TO BE INSPECTED 5. RECALL INSPECTION AFTER CORRECTIONS MADE |
|
| 05/13/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK GROUNDING & CONDUITS BELOW BLD. SLAB #202 |
|
| 04/23/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE LABEL DISCONNECT OR METER AS TO BLD. # |
|
| 03/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 02/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* WHEN CALLING INSP. LEAVE MSG. AS TO WHAT YOU WANT INSPECTED. |