Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/10/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 11/27/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* 1) OK REMAINDER OF SERVICE SECONDARY RACEWAY COVER 2) OK GROUND RING/BOND WHIPS 3) OK SERVICE GROUND RODS |
|
| 11/26/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RING TO HAVE MINIMUM 30" COVER (EARTH) 2. SERVICE GROUND RODS TO BE MINIMUM 6' APART |
|
| 11/16/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK PARTIAL SECONDARY RACEWAY COVER - NOT TURNED UP AT SERVICE & NOT ACROSS DRIVE YET. INSTALL WARNING RIBBON WHEN YOU BACKFILL. OTHER RACEWAY IN DITCH NOT APPROVED. |