Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T07CM02462
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2007 | MECHANICAL - FINAL | Approved | ||
09/17/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FIRE DAMPER NOT INSTALLED CORRECTLY PROVIDE INSTALL INSTRUCTIONS |
|
09/14/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/13/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PLEASE CLARIFY FIRE DAMPERS SHOWN ON PLAN DUCTING IN THIS AREA NOT PER PLAN |
|
09/11/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FINISH CONDENSATE DRAIN CONNECTIONS SOME TRAPS INSTALLED BACKWARDS |
|
09/07/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* PLANS SHOW FIRE DAMPERS. WHERE ARE THEY? PROVIDE SECONDARY DRAINS OR OVERFLOW SENSORS SOME CONDENSATE DRAINS BACK SLOPED I.D FAN COILS FAN COIL #54, FILTER CANNOT BE REMOVED PERMANENTLY I.D CONDENSORS & DISCONNECTS INSTALL REGISTERS PROVIDE AIR BALANCE REPORT |