Permit: T07CM02443
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/29/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO ENERGIZE PANEL AC 2. NEED PROTECTIVE BUSHING ON CONDUCTORS #4 & LARGER 3. NEED TO INSTALL SERVICE RECEPTACLE WITHIN 25' OF AC UNITS 4. BLANK OPEN KNOCKOUTS BACK OF VFD 5. NEED APPROVED DRAWING E-3 |
|
| 01/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SERVICE INSPECTION: DID NOT INSPECT 12" X 12" WIREWAY 2) HOUSE APPROVED PLANS |
|
| 01/16/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* MEETING FOR VISUAL INSPECTION OF EXISTING CT ENCLOSURE 1. BOND SERVICE RACEWAYS - NEW AND EXISTING 2. REMOVE UNNEEDED BOND WIRE TO DISCONNECTS |
|
| 01/03/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CONSULTATION ONLY @ THIS TIME - WORK IN PROGRESS |
|
| 12/19/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* |