Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/16/2008 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/27/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 2ND LAYER OF WRAP PROGRESSING |
|
| 03/26/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1ST LAYER OF FIRE WRAP OK OK FOR 2ND LAYER |
|
| 03/21/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DO NOT USE FOIL TAPE OR FIRE WRAP JOINTS BANDING IS REQUIRED ON BOTH LAYERS OF FIRE WRAP PROVIDE INSTALL INSTRUCTIONS FOR FIRE WRAP |
|
| 03/18/2008 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCTS OK 1ST LAYER OF FIRE WRAP |