Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM02433
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/26/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/22/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* WATER TEST DWV THRU ROOF OK 1. PROVIDE CORRECT DRAINAGE FITTING FOR URINAL 2. PROVIDE 2-HOLE STRAPS IN PLACE OF PLUMBERS TAPE WHERE REQUIRED 3. INSTALL WATER HEATER PER DETAIL 4. PROVIDE INSULATION 8' IN AND 8' OUT OF WATER HEATER PER 2006 ENERGY CONSERVATION CODE |