Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 03/31/2008 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 03/31/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) FINISH GROUNDING TO PANELS 2) INSTALL PROPER SIZE GROUND TO A/C UNIT 3) OK CEILINGS |
|
| 03/27/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. INSTALL MAIN BONDING JUMPER 2. INSTALL EQUIPMENT GROUNDING CONDUCTORS NEED PROPER SIZE 3. MARK "SERVICE DISCONNECT" 4. BOND SERVICE RISERS - NEC 250.92 5. REMOVE OBJECTIONABLE CURRENT ON EQUIPMENT GROUNDING CONDUCTORS - NEC 250.6 6. BOND WATER PIPE 7. FINISH WORK @ PANELS 8. OK CEILINGS DINING ROOM ONLY |