Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 09/05/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRICAL INTERMEDIATE NEVER PASSED 2) NEED TO ADD WALL MECH UNIT TO PLANS/REVISE ELECTRIC 3) NEED TO ADD BREAKERS/PLUG OFF UNUSED OPENINGS AT MAIN 4) NEED ALL CIRCUITS LABELED AT MAIN 5) NEED TO SHOW DELETION OF DUCT WORK TO ADDITION 6) NEED TEMPERED WINDOW WITHIN 24" OF DOOR TO EXTERIOR 7) NEED TO SHIELD EXTERIOR LIGHT 8) NEED POSITIVE DRAINAGE AWAY FROM STRUCTURE 9) NEED INSULATION CERT 10) WIRES AT EXTERIOR WALL ? EXPOSED |
|
| 08/30/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO ONE PRESENT FOR ACCESS AT 12:30 2 PLEASE RECALL |