Permit: T07CM02364

Parcel: 13104399H


Addresses:

4777 E 29TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/11/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2007 ELECTRIC - FINAL Cancelled IVRS - RI canceled
07/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS - NEC 250.8
2. BACK FED BREAKERS TO BE SECURED IN PLACE BY ADDITIONAL FASTENER -- NEC 408.16
3. GROUNDED CONDUCTORS NEED TO TERMINATE IN PANEL BOARD -- NEC 408.21
4. UNDERGROUND PVC BACKFILLED WITH NO INSPECTIONS.
EXPOSE PVC EVERY 15'-20' NEED TO EXPOSE COUPLINGS IN SEVERAL PLACES ALSO, NEED TO SEE WRITING ON PVC.