Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/31/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 07/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CANNOT USE SHEETMETAL SCREWS FOR GROUND CONNECTIONS - NEC 250.8 2. BACK FED BREAKERS TO BE SECURED IN PLACE BY ADDITIONAL FASTENER -- NEC 408.16 3. GROUNDED CONDUCTORS NEED TO TERMINATE IN PANEL BOARD -- NEC 408.21 4. UNDERGROUND PVC BACKFILLED WITH NO INSPECTIONS. EXPOSE PVC EVERY 15'-20' NEED TO EXPOSE COUPLINGS IN SEVERAL PLACES ALSO, NEED TO SEE WRITING ON PVC. |