Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 08/22/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PVC RACEWAYS TO BE MIN. 18" DEEP TO TOP OF RACEWAY NEC 300.5 2. RECALL AFTER 3/4" PVC HAS BEEN REINSTALLED TO PUMP STATION. |
|
| 07/13/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |