Permit: T07CM02362

Parcel: 141340150

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM02362

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/28/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
10/18/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) INSTALLED HTP410 2,170 POUNDS-REQUIRED HTU262=3,600-3800 POUNDS
10/01/2007 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) OK PER TRUSS ENGINEERS APPROVAL ON HTP410 IN RAFTERS
09/28/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TRUSS MANUFACTURERS APPROVAL ON HTP410 IN RAFTERS
2) HORIZONTAL BLOCK AND NAIL SHEARWALLS BY STAIR WELL
3) H25 PARAPET WALL NORTH END OF ROOF
4) FINISH NAILING ROOF NORTH END
09/19/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GLT 3 HANGER NOT INSTALLED USP TYPE INSTEAD HAVE LOAD/HANGER JUSTIFIED
2) NEED WIND BRACE 2ND FLOOR WEST/SOUTH
3) MISSING NAILING ON ROOF MARKED IN ORANGE
4) INSTALL CST 14 STRAPS #8 ON H.D. SCHEDULE AT FRONT 2ND FLOOR POP OUTS AND AT FRONT ENTRY
5) NAIL DIAGONAL BLOCKING IN SHEAR PANELS AT STAIRWELL
6) A35'S NEEDED TOP ABOVE GARAGE ON STUDS