Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02355
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/17/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1/2" EMT & 3/4 SPARE UP HOOD DUCT SHAFT |
|
11/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK PANEL WALL COVER AND CLOTHES CLOSET |
|
11/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS & SOFFITS EXCEPT PANEL WALL 1. FINISH PANEL WALL |
|
11/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO MORE THAN 360 DEG. IN A CONDUIT RUN 2. SUPPORT MC CABLES WITHIN 12" OF BOXES & CANS 3. JUNCTION BOX TO BE ACCESSIBLE |
|
11/01/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
10/25/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE PROTECTION FOR PVC AT BASE PLATE 2. FINISH VDV CABLING IN WALLS 90.4, 725.6, 800.6 3. PROTECT M/C IN STUD CHANNELS OR MOVE OUT 4. SECURE M/C CABLE 12" OF BOXES |
|
10/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 3/4" PVC INSTALLED UNDER SLAB |