Permit: T07CM02355

Parcel: 12404100A


Addresses:

845 N PARK AV #125

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/08/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1/2" EMT & 3/4 SPARE UP HOOD DUCT SHAFT
11/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK PANEL WALL COVER AND CLOTHES CLOSET
11/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS & SOFFITS EXCEPT PANEL WALL

1. FINISH PANEL WALL
11/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NO MORE THAN 360 DEG. IN A CONDUIT RUN
2. SUPPORT MC CABLES WITHIN 12" OF BOXES & CANS
3. JUNCTION BOX TO BE ACCESSIBLE
11/01/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED
10/25/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROVIDE PROTECTION FOR PVC AT BASE PLATE
2. FINISH VDV CABLING IN WALLS 90.4, 725.6, 800.6
3. PROTECT M/C IN STUD CHANNELS OR MOVE OUT
4. SECURE M/C CABLE 12" OF BOXES
10/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 3/4" PVC INSTALLED UNDER SLAB