Permit: T07CM02350

Parcel: 115044340


Addresses:

834 E HELEN ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02350

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/02/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED GFCI IN BATHROOM
2) IN SUB-PANEL, NEED SEPERATE NEUTRAL GRD WIRES, INSTALL GRD BAR, BUSHING AT KNOCKOUT, SQUARE D BREAKER USED IN MURRAY PANEL
3) PLUMBING VENTING FOR SHOWER, UNCOVER 2" DRAIN TO MAIN, OR SHOWER CONNECTION TO SEWER, UNCOVER BLDG SEWER CONNECTION
4) AT NEXT INSPECT WILL CUT SMALL INSPECTION HOLE TO SPOT CHECK FOR ROMEX PROTECTION AT METAL STUDS
5) WORK DONE WITHOUT PREVIOUS INSPECTIONS OR PERMIT
6) NEED TO RAISE VENT ABOVE ROOF LINE AND SECURE PLUMBING TO WALL