Permit: T07CM02348

Parcel: 115180050


Addresses:

1601 N ORACLE RD 09

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/08/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
04/03/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. WALK IN CONDENSORS NOT FUSED
2. WALK IN EVAP. COILS TO BE TRAPPED AT CONDENSATE PIPING

KITCHEN BALANCE REPORT OK
EXHAUST & MUA INTERLOCK OK
03/31/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EXHAUST FAN GREASE TRAPS NOT INSTALLED
2. NO POWER TO EXHAUST AND MAKE UP AIR
3. WALK INS NOT COMPLETE, NO TRAPS @ EVAPS
4. STORAGE RM 126, REMOVE GRILL FROM CEILING
PATCH HOLE
5. TYPE 1 EXHAUST FANS TO HAVE HINGE KITS PER 506.5.3 IMC
6. A/C CONDENSING UNITS NOT OPERABLE
03/25/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/20/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
SECOND LAYER GREASE DUCT WRAP OK
03/14/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
FIRST LAYER OF FIRE WRAP OK
03/10/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
OK TO WRAP GREASE DUCT
02/29/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*