Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/08/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 04/03/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. WALK IN CONDENSORS NOT FUSED 2. WALK IN EVAP. COILS TO BE TRAPPED AT CONDENSATE PIPING KITCHEN BALANCE REPORT OK EXHAUST & MUA INTERLOCK OK |
|
| 03/31/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXHAUST FAN GREASE TRAPS NOT INSTALLED 2. NO POWER TO EXHAUST AND MAKE UP AIR 3. WALK INS NOT COMPLETE, NO TRAPS @ EVAPS 4. STORAGE RM 126, REMOVE GRILL FROM CEILING PATCH HOLE 5. TYPE 1 EXHAUST FANS TO HAVE HINGE KITS PER 506.5.3 IMC 6. A/C CONDENSING UNITS NOT OPERABLE |
|
| 03/25/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/20/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* SECOND LAYER GREASE DUCT WRAP OK |
|
| 03/14/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* FIRST LAYER OF FIRE WRAP OK |
|
| 03/10/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO WRAP GREASE DUCT |
|
| 02/29/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* |