Permit: T07CM02348

Parcel: 115180050


Addresses:

1601 N ORACLE RD 09

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/31/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
03/28/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/27/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. 705.1.1 2006 UPC CAULKED FLANGES
ALSO, AFTER INSPECTION A "DUTCHMAN" WILL HAVE TO BE INSTALLED
2. ALL FLANGES TO BE SECURED TO THE FLOOR
3. RELOCATED FLOOR SINK AT EINSTEIN'S - OK TO COVER
4. NO GAS ISOMETRIC - GENERAL NOTE #1 ON P-1 IS SIMPLY A NOTE TO SUPPLY GAS FROM A SEPARATE METER. PROVIDE APPROVED ISOMETRIC.
03/25/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/12/2008 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CLOSET FLANGES TO EXTEND 1/4" ABOVE FINISHED FLOOR
03/06/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REPAIR OF HOT & COLD WATER SUPPLY
IN RESTROOMS 112, 113 OK TO COVER WALLS
2. NEED TO EXPOSE CLOSET FLANGE IN RESTROOMS 106, 107
02/22/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/20/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
02/06/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
MAIN KITCHEN
- UNDERSLAB TRUNK LINE TO GREASE INTERCEPTOR INCLUDING RELOCATION OF 2 FLOOR SINKS AND ADDITION
OF 5 HAND SINKS.
- EOL CLEANOUT TO FLOOR HEIGHT @ FLOOR SINK
- IN WALL CLEANOUTS 4" @ HAND SINK & FLOOR SINK S.E CORNER OF KITCHEN
- TIE IN TO EXISTING WITH CIX PLASTIC MISSION BANDS
60LB. TORQUE SPEC. VERIFIED

OK TO COVER
01/15/2008 PLUMBING - INTERMEDIATE Partial Approval COVER UNDER SLAB DRAIN LINE IN EINSTEINS AT YOUR OWN RISK, MEETS CODE BUT RED LINE DRAWING HAS NOT BEEN APPROVED.

OK TO SHEET ROCK BACK OF BAR WALL (HOT AND COLD CU WATER SUPPLY)
01/03/2008 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
BAR AREA RED LINED INCLUDE ISO
REPAIR MADE IN WOMENS RESTROOM #107
PLEASE CALL INSPECTIONS THROUGH THE IVR SYSTEMS
10/31/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS AND FLOOR AT EINSTEINS
REPAIR AT TOILET ROOM 107 MADE OK
10/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. HORIZONTAL ABS OVERHEAD TO BE SUPPORTED
2. ALL VERTICAL PIPING TO BE SUPPORTED SEE P.2/6.4
3. PLAN CALLS FOR TYPE "L" COPPER
4. THIS IS FOR EINSTEIN'S ONLY