Permit: T07CM02348

Parcel: 115180050


Addresses:

1601 N ORACLE RD 09

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/01/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/14/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LAST ITEMS:
1. UNLISTED EQUIPMENT - CASH MACHINE
2. SUBMIT AS BUILTS FOR FINAL PLAN REVISION
04/11/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ABOVE CEILING WALKWAY:
1. FINISH SUPPORT VDV
2. FINISH SERVICE LIGHTS PER 210.70
04/10/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
04/09/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/09/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
FINISH 1, 2, 3 & 5 OF 4/7/08
OK KIT GFCI & HOOD CONTACTORS
04/08/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. KITCHEN RECEPTACLES TO BE GFCI PROTECTED 210.8
2. HOOD CONTACTOR ENCLOSURE: TAPE TO ENCIRCLE CONDUCTOR ENTIRE EXPOSE LENGTH
3. FINISH ITEM 1, 2, 3, 5, 6 AND 7 PREVIOUS INSPECTION
04/07/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. CANNOT TAPE A WHITE CONDUCTOR A COLOR
2. MULTIPLE TERMINATIONS ON LUGS
3. VERIFY LOADS AND TAPS FOR WEST AC'S
4. BOND DISCONNECT ENCLOSURES
5. LABEL ALL DISCONNECTS
6. FINISH PANEL LABELING
7. SEAL ROOF JACKS
8. SECURE SUPPORT STANDS TO STRUCTURE
9. TIGHTEN LOOSE FITTINGS
10. PROTECT SEALTITE FROM SHARP METAL EDGES
04/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
04/02/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
04/01/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES PER 314.20
2. ATTACH DISCONNECT TO STRUCTURE AND MAINTAIN WORKING CLEARANCES
3. STRAP CONDUITS TO EXISTING A/C
4. MAKE STORAGE AREA SAFE

OK ROOMS 114, 115 AND BREAK ROOM
03/31/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LISTING LABELS NOT TO BE APPLIED IF OTHER THAN BY TESTING AGENCY

OK FOR USAGE OF LOBBY, BAR, MAILROOM, FRONT BATHROOMS, RECEPTION OFFICES & EINSTEIN'S SUBJECT TO LEERAY'S DETERMINATION - UNLISTED EQUIPMENT TO BE USED.

OK PANEL "T"
03/27/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. LABEL PANEL DIRECTORIES 408.4
2. EXCESS PAINT ON DEVICE TERMINALS
3. LISTING LABELS CASH MACHINE & JUKE BOX
4. BAR & LOBBY EXITS TO BE AS PER 700.12
03/19/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) OK PANELS EB, M, M1, A TO ENERGIZE
2) CONTRACTOR TO MAINTAIN LOCKOUT/TAG OUT ON SERVICE AT ALL TIMES
03/17/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
RECEIVED LETTER FOR TORQUE

1. FINISH H2O BOND
2. BOND JUMPER TO BE SIZED PER 250.102 & 250.66
3. BREAKER FOR SWITCH GEAR NOT AS PER PLANS
4. SEPARATE CONDUCTOR FROM UNPROTECTED
BUSS BEFORE MAIN
03/10/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
BAR, LOBBY, MAIL ROOM, RESTROOMS AND EINSTEIN'S:

1. BOXES MORE THAN 1/4"
2. SECURE BOXES INTO WALL
3. GROUND HARDWARE TO LIGHT FIXTURES - GROUND TRAC'S
4. VERIFY LISTING OF ALL EQUIPMENT
5. NO POWER AT THIS TIME

OK IMC - 1 1/2" OUT TO TRAILER
03/03/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO SERVICE INSPECTIONS HAVE BEEN DONE AT THIS TIME
FINISH INSTALLING DEVICES
NOTE 314.20 BOXES MORE THAN 1/4" BACK
NOTE 725.6, 800.6, 300.11 PANEL LABELING TO BE AS PER 408.4
10/11/2007 ELECTRIC - FINAL Not ready for Inspection GEAR IS EXISTING IN QUESTIONABLE CONDITION. CODE VIOLATIONS ARE PRESENT. ANY FIELD MODIFICATION WILL NEED TO BE DONE BY A THIRD PARTY EVALUATION

PLANS DO NOT MATCH INSTALLED EQUIPMENT FOR CONDUCTORS OR LOADS

WORK APPEARS TO BE INSTALLED AT A LATER DATE THAN ORIGINAL INSTALL. CONDITION LOOKS TO HAVE NOT BEEN CODE COMPLIANT AT TIME OF WORK DONE.

RECEIVED CK#9050 FOR $150..