Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/01/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* PANEL WAY: 1. SEPARATE GROUND & NEUTRALS - REMOVE BONDING JUMPER 2. DO NOT ENERGIZE OK PANEL "F" OK PANEL "W-2" EXCEPT BREAKER TO "W-4" PANEL C, "K-1", "K" EXCEPT BREAKER TO "T" OK ABOVE CEILING ROOM 110 PANEL "T": A MANUFACTURES MAIN BREAKER AND HOLD DOWN IS NEEDED |
|
| 03/25/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* FINISH AS DISCUSSED |
|
| 03/24/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* FINISH ITEMS ON POOL INSPECTION REPORT |
|
| 03/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS COOK'S OFFICE OK TO TILE GRID CEILINGS EXCEPT KITCHEN |
|
| 02/26/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK KITCHEN 110 & CORRIDOR |
|
| 02/25/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 02/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE APPROVED PLANS, KITCHEN INSP. AS PER MESSAGE |
|
| 02/20/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL KITCHEN INSPECTION 1. DEMO ALL ABANDONED WIRING TO SOURCE 2. PROVIDE BACK SUPPORT FOR BOXES AS NEEDED 3. PROVIDE NAIL PLATES AS NEEDED OK PANEL WALL COVER COR 120 |
|
| 02/14/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CORRIDOR 120 OK BUT DO NOT ROCK AROUND PANEL UNTIL RICK SEES IT 2. SERVICE ROOM 111 - REPAIR OF EXISTING IN WEST WALL OK |
|
| 02/06/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* LOW BAR WALL MC CABLE TO 3 OUTLETS OK TO COVER CORRECTIONS NOTED BY RH MADE |
|
| 02/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK SWITCHES 116-119 OK BATHROOMS 112-115 OK 3 FLOOR BOX 110 1. PROTECT PIPES DURING BACKFILL |
|
| 01/03/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. PROTECT M/C CABLE AT TOP PLATE 2. FILL UNUSED OPENINGS IN BOXES 3. PREVENT DIELECTRIC CONTACT WITH M/C CABLE 4. PROTECT CONDUCTOR FROM SCREWS INSIDE OF BOX 5. SUPPORT CONDUIT UPON EXITING FLOOR |
|
| 12/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK CANS AND BOXES CEILING LOUNGE 2) OK PONY WALL LOBBY 2 VDV CABELING TO BE PER 725.6 AND 800.6 |
|
| 11/06/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. EXPOSED CONDUCTORS - CLOSE BOXES, SUPPORT OR REMOVE OLD NM CABLING AS PER CODE 2. BOXES MORE THAN 1/4" - 314.20 3. WHAT IS DRYWALL AROUND CANS? 4. FINISH #2 OF PREVIOUS INSPECTION OK PVC CONDUITS FOR AC UNITS OK WALL ROOM 101 |
|
| 10/25/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SECURE VDV CABLING AT RINGS 775.6 2. SUPPORT VDV CABLING ABOVE CEILING 725.3 & 6, 800.3 & 6 3. USE APPROVED STRAPS FOR MC 4. SUPPORT M/C CABLES WITHIN 12" OF CANS 5. NO MORE THAN 360 DEG. IN A CONDUIT RUN * JUNCTION BOXES TO BE ACCESSIBLE |