Permit: T07CM02348

Parcel: 115180050


Addresses:

1601 N ORACLE RD 09

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/01/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PANEL WAY:
1. SEPARATE GROUND & NEUTRALS - REMOVE BONDING JUMPER
2. DO NOT ENERGIZE

OK PANEL "F"
OK PANEL "W-2" EXCEPT BREAKER TO "W-4"
PANEL C, "K-1", "K" EXCEPT BREAKER TO "T"
OK ABOVE CEILING ROOM 110

PANEL "T":
A MANUFACTURES MAIN BREAKER AND
HOLD DOWN IS NEEDED
03/25/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH AS DISCUSSED
03/24/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
FINISH ITEMS ON POOL INSPECTION REPORT
03/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS COOK'S OFFICE
OK TO TILE GRID CEILINGS EXCEPT KITCHEN
02/26/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK KITCHEN 110 & CORRIDOR
02/25/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
02/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE APPROVED PLANS, KITCHEN INSP. AS PER MESSAGE
02/20/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL KITCHEN INSPECTION
1. DEMO ALL ABANDONED WIRING TO SOURCE
2. PROVIDE BACK SUPPORT FOR BOXES AS NEEDED
3. PROVIDE NAIL PLATES AS NEEDED

OK PANEL WALL COVER COR 120
02/14/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CORRIDOR 120 OK BUT DO NOT ROCK AROUND PANEL UNTIL RICK SEES IT
2. SERVICE ROOM 111 - REPAIR OF EXISTING IN WEST WALL OK
02/06/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
LOW BAR WALL MC CABLE TO 3 OUTLETS OK TO COVER CORRECTIONS NOTED BY RH MADE
02/05/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK SWITCHES 116-119
OK BATHROOMS 112-115
OK 3 FLOOR BOX 110

1. PROTECT PIPES DURING BACKFILL
01/03/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT M/C CABLE AT TOP PLATE
2. FILL UNUSED OPENINGS IN BOXES
3. PREVENT DIELECTRIC CONTACT WITH M/C CABLE
4. PROTECT CONDUCTOR FROM SCREWS INSIDE OF BOX
5. SUPPORT CONDUIT UPON EXITING FLOOR
12/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK CANS AND BOXES CEILING LOUNGE
2) OK PONY WALL LOBBY
2 VDV CABELING TO BE PER 725.6 AND 800.6
11/06/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. EXPOSED CONDUCTORS - CLOSE BOXES, SUPPORT OR REMOVE OLD NM CABLING AS PER CODE
2. BOXES MORE THAN 1/4" - 314.20
3. WHAT IS DRYWALL AROUND CANS?
4. FINISH #2 OF PREVIOUS INSPECTION

OK PVC CONDUITS FOR AC UNITS
OK WALL ROOM 101
10/25/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SECURE VDV CABLING AT RINGS 775.6
2. SUPPORT VDV CABLING ABOVE CEILING 725.3 & 6, 800.3 & 6
3. USE APPROVED STRAPS FOR MC
4. SUPPORT M/C CABLES WITHIN 12" OF CANS
5. NO MORE THAN 360 DEG. IN A CONDUIT RUN

* JUNCTION BOXES TO BE ACCESSIBLE