Permit: T07CM02347

Parcel: 12713078B

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02347

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/07/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS -- 314.20
2. EM LIGHTING TO BE ON CIRCUIT FOR AREA SECURED 700.12
3. PLEASE PROVIDE PANEL SCHEDULE AS PER 408.4
4. FINISH VDV AS PER PREVIOUS INSPECTIONS