Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02347
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS -- 314.20 2. EM LIGHTING TO BE ON CIRCUIT FOR AREA SECURED 700.12 3. PLEASE PROVIDE PANEL SCHEDULE AS PER 408.4 4. FINISH VDV AS PER PREVIOUS INSPECTIONS |