Permit: T07CM02342

Parcel: 14118001H

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM02342

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
09/20/2007 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) OK FOR CEILING TILES
2) PROVIDE CONDENSATE DRAIN
3) PROVIDE T-STAT FOR T F-1 WILL CHECK ON FINAL
09/20/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
09/18/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
FLEX DUCT NOT TO EXCEED 5' PER PLANS
PROVIDE COND. PIPING FOR BOTH AC UNITS
OK CEILING TILES FRONT AREA ONLY