Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02342
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL RECEIVED CK#1182 FOR $150.00 FROM MARK JONES FOR AFTER HOURS INSPECTION |
|
10/03/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. DISCONNECTS FOR INSTANT HOT CANNOT BE ABOVE CEILING MAX HEIGHT OF 6'7" 2. INSTALL LOCKING DEVICE FOR SIGN LIGHT BREAKER 3. SEE BUILDING INSPECTOR FOR TEMP C OF O RECEIVED CHECK FROM ALEXANDER BATES FOR $150 CHECK #125 FOR BEFORE HRS. INSPECTION. |
|
10/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SEAL OPEN KNOCK OUT IN DISCONNECT 2. DISCONNECT TO OPEN ALL CONDUCTORS TO EQUIPMENT REQUIRING SERVICING. CANNOT RUN SWITCH LEG THROUGH EQUIPMENT THAT CANNOT BE DISCONNECTED 3. EM LIGHT IN BACK AREA NOT OPERATING |
|
10/02/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FOR BEFORE HRS. INSP. CALL JASON JAWORSKY @ 909-5147 FEE OF $150.00 |
|
10/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL BONDING SCREW AT AC DISCONNECTS 2. INSTALL PROTECTIVE BUSHING ON FIELD INSTALLED WIRES TO AC UNIT 3. INSTALL DISCONNECTS ON INSTANT HOTS 4. CIRCUITS NOT SIZED PROPERLY TO INSTANT HOTS 5. MISSING REMOTE EM HEADS AT FRONT & REAR EXITS 6. EM LIGHTING NOT OPERATING PROPERLY 7. INSTALL LOCKING DEVICE FOR SIGN LIGHTS |
|
09/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
09/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |