Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02339
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* 1) CONNECT CAN LIGHTS 2) #8 CU ROMEX FOR FEEDER INSTALLED OK BY CONTRACTOR 3) NOTE: DON'T FORGET CONDENSATE FOR MINI-SPLIT |
|
08/11/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY OWNER |
|
08/08/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) SEE WIRE SIZE ON PANEL SCHEDULE 2) CLOSET TO HAVE NO SHELVES 3) INSTALL GROUND BUSS IN SUB-PANEL 4) L-FLASHING BEHIND STUCCO AT WALL UNDER WINDOWS 5) CONDENSATE WILL GO TO EXTERIOR |
|
08/05/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SUB-PANEL SCHEDULE CALLS FOR 50 AMP FEEDER ROMEX #8 IS RATED AT 40 AMPS 2) NEED TO ISOLATE NEUTRALS AND GRDS IN SUB-PANEL INSTALL NEW GRD BUSS 3) DOES MINI SPLIT REQUIRED CONDENSATION LINE ? 4) LIGHTS IN CLOSETS SEE ABOVE CLEARANCES, CAN WON'T FIT 5) SEE NOTES FROM STUCCO INSP LAST 8/1/08. |