Inspection History Details
Permit: T07CM02335
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/04/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 09/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ROOF: 1. SUPPORT CONDUITS 2. FILL UNUSED OPENINGS IN BOX |
|
| 09/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. DRYWALL TO BE WITHIN 1/8" OF BOXES 314.21 2. LIFT MASTER TO BE WIRED AS PER MANUFACTURES INSTRUCTIONS. 110.3 NOT CORD & PLUG CONNECTED. SECURE CONTROL WIRING TO ENCLOSURES. 3. PANEL DIRECTORY TO BE AS PER 408.4 - NO ABBREVIATIONS 4. FILL UNUSED OPENING IN TOP OF PANEL & BOXES -- 110.12 5. CONDUCTOR COLORS FOR UNGROUNDED CONDUCTOR TO BE AS PER 210.5 (C) 6. PLEASE PROVIDE ROOF ACCESS TO CHECK CONNECTIONS OF NEW CONDUCTORS 7. OUTDOOR FIXTURE IS NOT FULL CUT OFF AS PER PLANS 8. RESUPPORT CONDUIT FOR VDV CABLING IN ELECT ROOM 9. LOFT LIGHTING NOT SHOWN ON PLANS OR OFFICE ELECTRIC |
|
| 09/06/2007 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled |