Inspection History Details
Permit: T07CM02335
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 08/07/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
| 08/06/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NO MORE THAN 360 DEG. IN A CONDUIT RUN 2. TIGHTEN LOOSE FITTINGS 3. PROTECT MC CABLE AT STUDS 4. GROUND ALL METAL BOXES 5. PLANS CALL FOR EMT CONDUIT FOR ALL WORK |