Permit: T07CM02321

Parcel: 140141980


Addresses:

5501 S CASSIA WY

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
07/28/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
06/13/2008 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) REMOVE ONE COURSE OF BLK FOR BOND BEAM, INSTALL #4 HORIZ AND ADD ONE COURSE
2) 8" BOND BEAM #4 TO BE IN CENTER
3) OK PORCH UTILITY ROOM
02/22/2008 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING H.25 CLIPS AT 2 X 4 WALL TO 2 X 8 RAFTERS, STORAGE TO UTILITY ROOM
2) DRAWING CALLS FOR SCREWS (LAG) FROM NEW 2 X ? RAFTING TO EXISTING 2 X 8 RAFTERS
3) NEED TO UNCOVER OSB TO VERIFY 18" TWIST STRAP ON BEAM AT CORNER OF STORAGE ROOM
4) EXCAVATION/LAYOUT REBAR AND ZONE FROM PRIOR INSPECTION CALLED FOR A PACOMETER TEST ON EXISTING CARPORT. OWNER SHOWED VERIFICATION THAT WORK WAS DONE UNDER PERMITS IN APRIL 1997
5) NED TO ADD MASONRY PRE GROUT TO ACTIVITY FOR CARPORT-1ST 4' LIFT HAS ONLY BEEN APPROVED. MISSING VERTICAL REBAR 4" ON CENTER
6) NEED TO REMOVE BIRD BLOCK 3 PLACES TO VERIFY A.A. IN TOP PLATE AT PORCH
7) OK TO DRY IN ROOF ON BACK PORCH. UTILITY ROOM AND STORAGE ROOM ROOFS ONLY
8) CARPORT HAS NOT BEEN INSPECTED