Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T07CM02319
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2008 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* CONTRACTOR TO BACK FILL WITH CLEAN FILL |
|
| 06/25/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/24/2008 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* - YOU HAVE NOT INSTALLED THE PLUMBING PER THE PLAN - THE ISLAND SINK SHOWS A CHICAGO LOOP - YOU HAVE NOT INSTALLED IT PER PLAN - MINIMUM WASTE PIPING SIZE FOR A SINK IS 2" - THE AAV IS IN THE WRONG LOCATION AND THE PIPING IS NOT PER PLAN - WRAP ALL PIPING PASSING THROUGH THE MASONRY - ALL PIPING REQUIRES A TEST CONTINUED "NOT READY" WILL RESULT IN A REINSPECTION FEE |
|
| 06/20/2008 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* FROM THE POINT OF VENT TO THE TRAP WEIR MAY BE ONLY 3'6" ON 1 1/2" TRAP ARM |