Permit: T07CM02319

Parcel: 124040720


Addresses:

1333 E 2ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02319

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/27/2008 ELECTRIC - FINAL Approved
08/20/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
HAVE ENGINEER SHOW LOADS AND VERIFY LOADS FOR PANELS DIFFERENT THAN PLANS - NEED 3RD PARTY STAMP

OK TCO SUBJECT TO BUILDING OFFICAL
08/18/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PANELS TO BE NO MORE THAN 1/4" BOX TO SURFACE WE HAVE 1 1/4"
2. SEPARATE GROUNDS AND NEUTRALS AT SUB-PANEL
3. WE HAVE 46 CIRCUITS IN A 42 CIRCUIT SUB-PANEL
4. REVISED CIRCUIT DIRECTORY TO BE AS PER 408.4 -
NO ABBREVIATIONS
5. METAL RINGS NOT LISTED FOR USE AS EXTENDERS
6. PLEASE VERIFY COMBUSTIBILITY OF WALL PAPER CARPET
7. CANNOT USE SHEETMETAL THREAD SCREW FOR GROUNDING - 250.8
8. FILL UNUSED OPENING IN FIXTURES
9. PROTECT CONDUCTORS FROM SHARP EDGES OF FIXTURES
10. DIMMERS NOT AS PER PLANS
11. PANEL SCHEDULES NOT AS PER PLANS
08/13/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*PARTIAL INSPECTION

1. KITCHEN RECEPTACLES TO BE GFCI PLANS & 210.8
2. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLES OR FLUSH IN NON-COMBUSTIBLES - 314.20
3. INSTALL RANGE ANTI-TIP 110.3
4. ABOVE COUNTER RECEPTACLES ON PLANS CALL FOR DOUBLE DUPLEX
5. PLEASE HAVE ELECTRICIAN PRESENT TO OPEN LIGHTS AND EQUIPMENT