Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02319
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/20/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/24/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CULTURAL HALL CEILING |
|
| 06/19/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WEST END CEILING OF CULTURAL CENTER |
|
| 06/02/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL & HARD LID COVER 3 ENTRY OFFICES, CEILING IN MULTI-PURPOSE ROOM, EAST SIDE KITCHEN WALL, AND KITCHEN AREA HARD LID, KITCHEN ISLANDS U.G |
|
| 05/23/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. JUNCTION BOXES ABOVE HARD LIDS TO BE ACCESSIBLE 2. SEAL OPEN KNOCK OUTS IN BOXES 3. GROUND ALL METAL BOXES 4. STRAP EMT & FLEX 5. REMOVE OLD EMT & LOW VOLTAGE WIRING OR INSTALL LOW VOLTAGE IF BEING REVISED 6. STRAP MC WITHIN 12" OF BOXES 7. INSTALL LOW VOLTAGE CABLES |