Permit: T07CM02319

Parcel: 124040720


Addresses:

1333 E 2ND ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T07CM02319

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/24/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CULTURAL HALL CEILING
06/19/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WEST END CEILING OF CULTURAL CENTER
06/02/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALL & HARD LID COVER 3 ENTRY OFFICES, CEILING IN MULTI-PURPOSE ROOM, EAST SIDE KITCHEN WALL, AND KITCHEN AREA HARD LID, KITCHEN ISLANDS U.G
05/23/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. JUNCTION BOXES ABOVE HARD LIDS TO BE ACCESSIBLE
2. SEAL OPEN KNOCK OUTS IN BOXES
3. GROUND ALL METAL BOXES
4. STRAP EMT & FLEX
5. REMOVE OLD EMT & LOW VOLTAGE WIRING OR INSTALL
LOW VOLTAGE IF BEING REVISED
6. STRAP MC WITHIN 12" OF BOXES
7. INSTALL LOW VOLTAGE CABLES