Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY POLE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/19/2007 | ELECTRIC - TEMPORARY POLE | Approved | IVRS - Inspection :* | |
| 06/18/2007 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SEE TABLE 400.5 (A) NEC MAX ALLOWABLE OVERCURRENT 40 AMPS |
|
| 06/15/2007 | ELECTRIC - TEMPORARY POLE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) #8 SO CORD OVER FUSED AT 60 AMPS |