Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T07CM02309
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/05/2008 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
02/04/2008 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* | |
01/09/2008 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) H.D. NEEDS TO BE NAILED PROPERLY AT STUDS 2) NEED TO INSTALL SUPPORT POST PER 13/A6 AT GARAGE 3) CST STRAP WRONG LOCATION ON NORTH EAST SHEARWALL 4) MISSING SIMPSON CONNECTION ON 6 X 6 POST AT GARAGE |