Permit: T07CM02302

Parcel: 13320020A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
RECEIVED CK#35458 FOR $108.00
09/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE LOCKNUTS
2. BOXES MORE THAN 1/4" NEED AN APPROVED EXTENDER RING
3. PANEL SCHEDULE TO BE AS PER 408.4 NO ABBREVIATIONS
4. FINISH VDV CABLING
5. GROUNDING EQUIPMENT CONDUCTOR TO BE GREEN OR BARE ENTIRE LENGTH 250.119
6. ONLY ONE CONDUCTOR PER LUG TERMINATION
7. MAINTENANCE RECEPTACLE TO BE WITHIN 25' -- 210.63
09/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/31/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*