Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T07CM02291
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2007 | FRAMING | Approved | IVRS - Inspection :* | |
08/17/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) NEED FULL SET OF STAMPED RAFTER ? |
|
08/15/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED FULL SET OF STAMPED RAFTER ? 2) TRUSS # SHOP DRAWINGS, CONFIGURATION OF WEBS DON'T MATCH INSTALLATION 3) CUT STUD AT STAIR LIGHT 4) CHECK OUT LEAK KIT CEILING TUB/ABOVE 5) MAKE SURE EXHAUST DAMPERS OPEN AND CLOSE SOME ARE JAMMED OPEN OR CLOSED 6) ROOF NAIL INSPECTION NOT SIGNED OFF |
|
08/14/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DRAFT STOP 2ND FLOOR TUBS 2) RAFTER AND TRUSS SPECS 3) LTT20 B HOLDOWN NEEDED BY FRONT DOOR 4) MAX 6" CENTERS ON NAILS IN SHEARWALL SINK PLATES UPSTAIRS 5) EXTEND WASHER DISASTER PIPE TO OUTSIDE OF STUCCO MESH 6) UFER GROUND 7) LEAK FROM TUBS ABOVE KITCHEN 8) NAIL PROTECT CLOSET SIDE OF DRYER DUCT AT TOP PLATE |