Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02281
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/15/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/12/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SECURE ANTENNA COAX AS PER 820.24 2. ANTENNA GROUNDING CONDUCTOR TO BE AS PER 810.21 3. USE APPROVED RACEWAY 820.133, 110.3 4. PREVENT ACCUMULATION OF MOISTURE INTO RACEWAY SYSTEM WITH APPROVED METHODS |
|
09/17/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY RAUL |
|
09/05/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK CAN LIGHTS SOFFITS & HARD LIDS 1. SUPPORT MC WITHIN 12" OF CANS |
|
08/30/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* JUNCTION BOXES & LIGHTS TO BE ACCESSIBLE OK WALLS |