Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 11/27/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : Install 2 ground rods 6 feet apart with a continuous grounding electrode connection You must provide proof of ufer ground inspection or install two 8 foot ground rods 6 feet apart and connected to service panel with a continous #4 ground wire. Next failure will be charged a reinspection fee |
|
| 11/20/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NO UFER INSPECTION NOTED 2) PROVIDE GROUND RODS |
|
| 11/19/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* 1) RELOCATE SERVICE |