Permit: T07CM02275

Parcel: 125080260


Addresses:

2212 E LA MIRADA ST


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T07CM02275

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
01/04/2008 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
12/07/2007 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE TRUSS MATTS SHOW LAYOUT BUT NOT HANGERS
2) SIMPSON REQUIRES 16D NAILS IN HPAD 22 HOLDOWNS. .102 X 3 1/4) YOU USED NAILS APPROX .121 X 3 1/4
3) ROOF NAILING OK, SUPPORT EDGES THAT ARE SAGGED WITH BLOCKING. OK TO DRY IN
4) NEED TRUSS CALCS TO CHECK TRUSS INSTALLATION. HANGERS TO GIRDER ?