Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T07CM02269
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/18/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
12/16/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CAULK 2ND DRAIN AT STUCCO 2) COMPLY WITH ITEMS #2 AND #6 3) NEXT TIME PROVIDE LADDER OF SUITABLE HEIGHT |
|
12/10/2008 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) NEED ALL CERTIFICATIONS FOR THIS HOUSE, STUCCO, INSULATION AND CONCRETE ATTIC AREA: 1) FURNACE NEEDS OVER FLOW DRAIN OR AUTO/SHUT OFF, AT PAN 2) U.L. LABEL MARKED NO HEAT STRIP 15 AMP OVER CURRENT 35 AMP FUSES INSTALLED 3) NEED VENT/P-TRAP ON PRIMARY LINE 4) PAN FULL OF INSULATION 5) STAT WIRE IS NOT PROTECTED FROM SHARP EDGE OF FURNACE CABINET WHERE ITPASSES THRU UNIT 6) 10" WIDE OSB NOT SUPPORTED AT PLATFORM |