Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2008 | FIRE - FINAL | Approved | Approved 4/4/08. | |
| 04/03/2008 | FIRE - FINAL | Denied | Not approved 4/3/08. Opening in ceiling and walls in hot water heater room. |
|
| 03/12/2008 | FIRE - FINAL | Denied | Denied 3/11/08. 1.) Need address numbers for building. 2.) Nedd cover plates in following areas: a. Apt.#9 b. Hot water heater room. c. room adjacent to hot water heater room. d. Apt. #1C e. Apt. #1D f. Maint. room X 3. 3.) Attic area over hallway, exposed wiring. 4.) Apt. #1D, open scuttle hole exposing attic space. 5.) Broken EXIT sign, 2nd. floor south end. 6.) Large openings in ceiling and wall in hot water heater room. 7.) Exposed wiring overhead area maint. room. 8.) Have wiring in hot water heater room inpected by electrician. 9.) ROMEX wiring 7 ft. or under from floor and ROMEX through wall shall be protected by conduit. |