Permit: T07CM02255

Parcel: 10408078C


Addresses:

660 W AUTO MALL DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/02/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
WEST TRAILER GONE
06/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) FINAL TO BE ALL APPROVED AFTER TEMPORARY WIRING IS NO LONGER NEEDED AND HAS BEEN REMOVED
06/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) HAVE PLANS ON SITE AND EQUIPMENT OPEN FOR INSPECTION
2) EQUIPMENT GROUND UNDERSIZED NEC 250.122 B
3) INSTALL 3R HOODS ON TRANSFORMER
4) MOVE CONDUCTORS TO LOAD SIDE OF DISCONNECT PER PLAN