Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* WEST TRAILER GONE |
|
| 06/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) FINAL TO BE ALL APPROVED AFTER TEMPORARY WIRING IS NO LONGER NEEDED AND HAS BEEN REMOVED |
|
| 06/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) HAVE PLANS ON SITE AND EQUIPMENT OPEN FOR INSPECTION 2) EQUIPMENT GROUND UNDERSIZED NEC 250.122 B 3) INSTALL 3R HOODS ON TRANSFORMER 4) MOVE CONDUCTORS TO LOAD SIDE OF DISCONNECT PER PLAN |