Permit: T07CM02253


Addresses:

3202 N ORACLE RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T07CM02253

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2007 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
12/10/2007 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
- PROVIDE HANGERS AT 5' MAX
- PROVIDE SADDLES ON HANGERS PER PLANS
- FIX DUCT WHERE TWISTED
- DUCT CANNOT BE USED TO SUPPORT OTHER DUCT
- MOVE RETURN FLEX SO AS NOT TO BLOCK ACCESS TO DUCT DETECTOR
- REGISTERS IN FRONT STAGE AREA HAVE FLEX DUCT TOO RESTRICTED
- REFER TO KEYNOTE 1 M1.0