Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T07CM02253
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/12/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/10/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* - PROVIDE HANGERS AT 5' MAX - PROVIDE SADDLES ON HANGERS PER PLANS - FIX DUCT WHERE TWISTED - DUCT CANNOT BE USED TO SUPPORT OTHER DUCT - MOVE RETURN FLEX SO AS NOT TO BLOCK ACCESS TO DUCT DETECTOR - REGISTERS IN FRONT STAGE AREA HAVE FLEX DUCT TOO RESTRICTED - REFER TO KEYNOTE 1 M1.0 |