Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02253
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/29/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/21/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ITEMS ON LIST (2-15-08) OK EXCEPT NOTE #1 CAN LIGHTS NOT WORKING OK FOR TCO SUBJECT TO OTHER INSPECTOR APPROVALS |
|
02/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY ENTRY CANS (2) NOT WORKING 2. INSTALL ARC SHIELDS AS REQUIRED - NEC 314.20 3. OFFICE FURNITURE REQUIRES 3 POLE BREAKER - NEC 605.6, 605.7 4. NEED TO INSPECT CONDUCTORS & FUSE SIZE PANEL "Z" AND ROOF SERVICE RECEPTACLE |