Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02250
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/03/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/29/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS ITEMS 2 & 3 2. MAINTAIN WORKING CLEARANCES AT PANELS |
|
05/12/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMERGENCY LIGHTS TO BE AIMED DOWN AND OUT SO THEY WILL BE EFFECTIVE 2. PANEL DIRECTORY TO BE PROPERLY AND COMPLETELY IDENTIFIED FOR CKT'S FEEDING THIS OFFICE 3. MC TO BE SECURED WITHIN 12" OF TERMINATIONS FOR E-LIGHT 4. PROVIDE LADDER & ACCESS TO PANELS |
|
04/11/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLANS SHOW EXIT LIGHT 2. MOUNT FLOOR RECEPTACLE 3. INSTALL ALL DEVICE COVER PLATES 4. NEED ACCESS TO PANELS |