Permit: T07CM02243

Parcel: 13348128F


Addresses:

100 S HOUGHTON RD

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Date Description Inspector Results Comments
03/27/2008 MECHANICAL - HOODS Approved IVRS - Inspection :*
03/05/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
FIRE WRAP PROGRESSING
WILL CHECK FINAL WRAP AND ACCESS DOOR ON FINAL INSPECTION.
RELOCATE DUCT SMOKE DETECTOR TO ACCESSIBLE LOCATION
03/04/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1ST LAYER FIRE WRAP OK
OK FOR SECOND LAYER
02/27/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
PARTIAL 1ST LAYER OF FIREWRAP
BANDING OK
OK TO PROCEED WITH 1ST LAYER & ACCESS DOOR
02/26/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
- CHECKED WELDS ON GREASE DUCTS
- OK FOR 1ST LAYER OF FIRE WRAP
- DON'T FORGET TO PROVIDE THE REQUIRED HEAT SENSOR & ELEC. DETAIL ON PLANS
02/22/2008 MECHANICAL - HOODS Not ready for Inspection IVRS - Inspection :*
PLEASE PROVIDE A LADDER TO GET ON TOP OF HOOD
PROVIDE A MIN. 100 WATT LIGHT INSIDE DUCT FOR INSPECTION ON WELDS
02/06/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
- CHECKED WELDS ON GREASE DUCTS PRIOR TO INSTALLATION
- OK TO INSTALL
- NEED TO SEE WELDED JOINTS PRIOR TO FIRE WRAP
- PROVIDE INSTALL INSTRUCTIONS FOR FIRE WRAP
- FIRE WRAP MUST MEET ASTME 2336 REQUIREMENTS
- DO NOT TAPE JOINTS & SEAMS - CANNOT CONFIRM MIN. OVERLAP.
01/29/2008 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
1ST 4' OF DUCT FROM ROOF OK TO WRAP