Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T07CM02243
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2008 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
03/05/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* FIRE WRAP PROGRESSING WILL CHECK FINAL WRAP AND ACCESS DOOR ON FINAL INSPECTION. RELOCATE DUCT SMOKE DETECTOR TO ACCESSIBLE LOCATION |
|
03/04/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1ST LAYER FIRE WRAP OK OK FOR SECOND LAYER |
|
02/27/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* PARTIAL 1ST LAYER OF FIREWRAP BANDING OK OK TO PROCEED WITH 1ST LAYER & ACCESS DOOR |
|
02/26/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* - CHECKED WELDS ON GREASE DUCTS - OK FOR 1ST LAYER OF FIRE WRAP - DON'T FORGET TO PROVIDE THE REQUIRED HEAT SENSOR & ELEC. DETAIL ON PLANS |
|
02/22/2008 | MECHANICAL - HOODS | Not ready for Inspection | IVRS - Inspection :* PLEASE PROVIDE A LADDER TO GET ON TOP OF HOOD PROVIDE A MIN. 100 WATT LIGHT INSIDE DUCT FOR INSPECTION ON WELDS |
|
02/06/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* - CHECKED WELDS ON GREASE DUCTS PRIOR TO INSTALLATION - OK TO INSTALL - NEED TO SEE WELDED JOINTS PRIOR TO FIRE WRAP - PROVIDE INSTALL INSTRUCTIONS FOR FIRE WRAP - FIRE WRAP MUST MEET ASTME 2336 REQUIREMENTS - DO NOT TAPE JOINTS & SEAMS - CANNOT CONFIRM MIN. OVERLAP. |
|
01/29/2008 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* 1ST 4' OF DUCT FROM ROOF OK TO WRAP |