Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T07CM02243
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
03/20/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SIGNS TO BE MARKED PER NEC 600.4 2. SIGNS TO BE LISTED - NEC 600.3 3. SIGNS TO HAVE DISCONNECT PER NEC 600.6 4. FLEXIBLE CORDS CANNOT BE RUN THROUGH CEILING TILES OR ABOVE DROP CEILINGS - NEC 400.8 5. EM LIGHTING NOT PER PLAN |
|
03/19/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE REVISION FOR CHANGE IN EQUIPMENT 2. SECURE EMT RUN ON ROOFTOP AS DISCUSSED 3. PROPERLY INSTALL GROUNDS IN AC DISCONNECT |
|
03/17/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |