Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T07CM02243
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/26/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
02/05/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALLS |
|
01/31/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEAL OPEN KNOCK OUT IN JUNCTION BOX UNDER HOOD 2. PLANS DO NOT ALLOW USE OF MC CABLE PLEASE PROVIDE LETTER FROM ARCHITECT TO ALLOW USE 3. STRAP EMT WITHIN 3' OF PANEL. DO NOT BELIEVE THIS IS DONE CANNOT TELL BECAUSE WALL ABOVE PANEL HAS BEEN CLOSED. |