Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/05/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* AIR BALANCE OK |
|
| 05/09/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* - DO NOT USE CONDUITS & PIPES TO SUPPORT FLEX DUCTS - ADEQUATELY SUPPORT FLEX DUCTS - NO SAGS ALLOWED - CD & FLEX DUCT NOT INSTALLED PER DETAIL ON PLANS - MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY |