Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2008 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
| 02/21/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* | |
| 01/11/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* AIR TEST OK |
|
| 01/10/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* CONTINUATION OF 4" SDR TO BUILDING OK WILL AIR TEST AFTER COVERING NEED TO SEE CONNECTION AT BUILDING WILL NEED FULL SIZE UPPER TERMINAL CLEANOUT |
|
| 01/03/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* AIR TEST FROM HCS TO FIRST CO OK |
|
| 01/02/2008 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* 4" SDR TO PROP. LINE PER C-1 DRAWING APPROVED 12/27/07 OK SUBJECT TO TEST |
|
| 12/28/2007 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* CONTRACTOR CANCELLED |
|
| 12/27/2007 | PLUMBING - SEWER HCS CONNECT | Not ready for Inspection | IVRS - Inspection :* 1) PROVIDE CITY APPROVED SITE PLAN FOR 4" SEWER FROM EAST SIDE OF BEAR CANYON TO BLDG 2) 40' FROM PUBLIC MAIN 4" SDR 35 LAYED INCLUDING TAP OF MAIN, BEDDING LAYING , ? TO BE TESTED AT LATER DATE AND ENGINEER OR LICENSED SURVEYOR TO PROVIDE VERIFICATION OF GRADE 3) CONTACT ROBER SHERRY C OF T PLUMBING PLAN CHECK |