Permit: T07CM02238

Parcel: 11451203C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T07CM02238

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/03/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/02/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL DATA AT FRONT COUNTER TO INSPECT PHYSICAL PROTECTION
2. FINISH MOVING DISCONNECT BELOW CEILING
07/01/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELED
06/27/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
ROOF:
1. SUPPORT CONDUIT STUBS OVER 6"
2. MAINTENANCE RECEPTACLES TO BE HOT WITH
DISCONNECT OFF
3. CLEAN SURFACE UNDER LUGS

1. EXIT LIGHTS NOT WORKING
2. DISCONNECT FOR DOOR MOTOR TO BE ADJACENT TO MOTOR NOT ABOVE CEILING
3. FRONT COUNTERS NOT INSTALLED
4. EM/NIGH LIGHTS NOT WORKING
5. FIRE ALARM CABLE NOT FOR NORMAL POWER TO OCCUPANCY SENSOR
6. WHERE ARE RECEPTACLES FOR CIR LA-25?