Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T07CM02238
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 05/13/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* | |
| 05/06/2008 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. A BOND WILL NEED TO BE POSTED FOR TEMP POWER 2. MARK PANEL OUTSIDE COVERS PER 200.5 3. CANNOT STACK LUGS 4. USE CORRECT SIZED STRAP FOR FLEX 5. LABEL DISCONNECT AT SERVICE 6. DEVICES BELOW 8' TO BE PLATED OR BLANKED |